Control Techniques HVAC Drive H300 AC (VFD) Drives

The HVAC Drive H300, part of the newly introduced Specialist series of industry-specific drive technologies, builds on our company’s five decades of drives expertise, delivering precisedependable flow control.

The HVAC Drive H300 dimensions are among the smallest in its class at every power rating. This saves valuable building real estate, makes the drives easy to handle, and maximizes mounting flexibility.

Features
A complete HVAC/R building automation solution

HVAC Drive H300 has all of the features you would expect from a dedicated HVAC AC drive, including:

  1. Easy integration with Building Automation Systems with onboard BACnet, Metasys N2 and Modbus RTU communications
  2. Flexibility without a Building Management System with optional co-processor for running custom application software
  3. Fire mode for occupant safety which allows the drive to continue to run in the event of a fire for smoke extraction or pressurizing a room
  4. Quiet operation with Rotor Flux Control modeshigh switching frequencies (up to 16 kHz), and an intelligent 10 speed drive cooling fan with minimum noise operation
  5. High product reliability with conformally coated PCBs as standard
  6. Easy system installation and ongoing management with intuitive PC tools and useful VFD features
  7. High energy efficiency, up to 98%
  8. Dynamic Volts/Hertz energy optimization
  9. Sleep, Wake, and VFD standby modes
  10. Motor control of super high efficiency sensorless permanent magnet motors
  11. Among the most compact VFD in its class at every frame size
Specifications
Performance
  1. Normal Duty peak rating: 110 % (60 s)
  2. Maximum output frequency: 550 Hz
  3. Switching frequency range: 2, 3, 4, 6, 8, 12, 16 kHz (3 kHz default)
  4. Sensorless permanent magnet motor control
Onboard communications
  1. RS485 (BACnet, Metasys N2, Modus RTU)
Parameter backup
  1. Serial port cloning with complimentary Connect Software
  2. SD memory card (using SD-SMARTCARD-ADAPTOR)
  3. SMARTCARD reader support
  4. PC tools
Onboard I/O
  1. 2 x Analog inputs, 2 x Analog outputs
  2. 3 x Digital inputs, 3 x Bidirectional digital inputs or outputs
  3. 2 x Relay outputs (Form C)
Machine safety / VFD enable
  1. 1 x Safe Torque Off (STO) terminal
Power and motor control
  1. Stationary autotune for sensorless permanent magnet motors
  2. Wide operating Voltage range, capability to operate on a back-up DC supply
  3. 24 V control backup
Other
  1. Temperature controlled 10 speed fan operation with user adjustable speed limit
  2. User replaceable fan(s) for easy maintenance
  3. PCB conformal coating
  4. Sleep, Wake, and VFD Standby modes (energy saving)
VOLTAGE RATINGS
100 V (100 V – 120 V ± 10%)
200 V (200 V – 240 V ± 10%)
400 V (380 V – 480 V ± 10%)
575 V (500 V – 575 V ± 10%)
Approval & Listings
cUL USA and Canada (cUL Listed). UL File number: E171230
CE European Union (all applicable directives and regulations LVD, EMD, RoHS, REACH, Energy related products)
UKCA United Kingdom (all applicable regulations)
RCM Australia and New Zealand (Responsible Supplier Registration No. E6934)
EAC Russian Customs Union. H300 models
Functional Safety Safe Torque Off function.
TÜV Rheinland Type Examination Certificates:
01/205/5270.02/17 (Unidrive-M and derivative products)
01/205/5409.02/21 (SI-Safety  option module)
01/205/5720.00/19 (MiS210, MiS250 option modules)The safety function “Safe Torque Off” can be used in applications up to Cat 4. PL e according to EN ISO 13849-1, SIL 3 according to EN 61800-5-2/ EN 62061/ IEC 61508, and in lift applications according to EN 81-1 and EN81-2.
UL Functional Safety Unidrive-M all products
File E171230 Vol. 11 Sec. 1 Issued: 2015-01-22
Compliance with specific requirements of NFPA 79
ISO Quality system: ISO 9001 (Certificate Nos. FM 739405)
Environmental management system: ISO 14001 (Certificate No. EMS 739789)
Occupational health and safety: ISO 45001 (Certificate No. 5430)
China RoHS Chinese Order No. 32, 2016; Administrative Measures for the Restriction of Hazardous Substances in Electrical and Electronic Equipment (China RoHS 2),
EPA TSCA regulations All Commander and Unidrive-M products
U.S. Environmental Protection Agency (“EPA”) recently promulgated regulations under the Toxic Substances Control Act (“TSCA”)
IHM, Basel convention, MEPC 68/21 / Add.1, Annex 17, Resolution MEPC.269(68) 2015 Guidelines for the development of the inventory of hazardous materials.
Responsible Minerals Initiative (RMI) CMRT compliance
Weights & Dimensions
FRAME SIZE    DIMENSIONS (H x W x D) WEIGHT
mm in kg lb
3 382 x 83 x 200  15.0 x 3.3 x 7.9 4.5 max 9.9 max
4 391 x 124 x 200 15.4 x 4.9 x 7.9 6.5 14.3
5 391 x 143 x 200 15.4 x 5.6 x 7.9 7.4 16.3
6 391 x 210 x 227 15.4 x 8.3 x 8.9 14 30.9
7 557 x 270 x 280 21.9 x 10.6 x 11.0 28 61.7
8 804 x 310 x 290 31.6 x 12.2 x 11.4 52 114.6
9E 1069 x 310 x 290 42.1 x 12.2 x 11.4 46 101.4
10E 1069 x 310 x 290 42.1 x 12.2 x 11.4 46 101.4
11E 1242 x 310 x 312 55.5 x 12.2 x 12.3 63 138.9

Dimensions include mounting brackets